Modular Aluminum Compressed Air Piping Installation Instructions 3/4”-2”
PLANNING/LAYOUT
Before beginning the installation, create a plan as to the location of the air compressor and where you are
going to mount the compressed air outlets. On the plan locate outlets, tees, and elbows.
AIR COMPRESSOR
Use a flexible jumper hose from the air compressor to the filter regulator unit to reduce vibration to the
FastPipe System.
FILTER REGULATOR
A filter regulator unit is reccomended to keep
contaminants out of the air system and to allow for
pressure adjustment.
PRESSURE RATINGS
The FastPipe system has a maximum working pressure
of 190 psi and a temperature range from 0 to 140 deg F.
ASSEMBLY OF THREADED COMPONENTS
Assemble all NPT threads with two wraps of teflon tape
and then PIPE SEALANT which prevents thread galling.
IF YOU ARE EXPERIENCING TROUBLE WITH THIS PRODUCT, OR
MISSING PARTS, PLEASE CALL 800-954-3310 FOR ASSISTANCE
DO NOT RETURN TO STORE
•
Use pipe clips to secure pipe to any flat surface with
mounting screw
• Ceiling or wall mount
•
Clip has 5/16” thru hole and hex bore for a 5/16” hex nut
•
Hex nut serves at a backer for screws
• Use #10 Drywall Screw or Tapcon
•
In horizontal installations, mount clip pivot tab up
• Hangers or mounting clips should be no more than
10 ft apart and one must be at least 6” from a fitting
FLAT SURFACE INSTALLATION
HANGING INSTALLATION
• Beam Clamp
• 5/16” Threaded Rod
• Pipe Clip
• Beam Clamp
• 3/8” Threaded Rod
• Pipe Clip
EXPANSION JOINTS
TEMP
CHANGE
10°F
20°F
35°F
55°F
70°F
3/4” 1” 11/2” 2”
MAXIMUM STRAIGHT RUN DISTANCE
700ft
500ft
350ft
260ft
200ft
550ft
420ft
280ft
200ft
170ft
600ft
460ft
310ft
230ft
190ft
500ft
370ft
250ft
190ft
150ft
Any piping system will expand and contract with temperature changes, use this
guide for installation of expansion joints to compensate for this movement of
aluminum pipe in non-conditioned buildings
Pipe Clip
Strut Cushion Clamp