Chapter 5: Using the Web Interface
125
To enable the hysteresis, type a non-zero value, which must meet
the rules described in the table:
Threshold
Criterion
Upper critical threshold
Larger than or equal to the following
formula:
upper non-critical thr hysteresis
Upper non-critical threshold Larger than or equal to the following
formula:
lower non-critical thr (2 x
hysteresis)
Lower non-critical threshold Larger than or equal to the following
formula:
lower critical thr hysteresis
7. Click Apply. The sensor settings are saved.
8. If necessary, select another managed sensor from the "Show setup of
external sensor" drop-down list, and repeat these steps to configure it.
Note: The number in parentheses following a sensor name is the ID
number assigned to each sensor.
Note: The maximum ambient operating temperature (TMA) for the
Dominion PX varies between 40 to 60 degrees Celsius, depending on the
model and certification standard (CE or UL). If necessary, contact Raritan
Technical Support for this information for your model.