Chapter 8: Inline Monitors
198
Manual Mode
You can switch between voltage, active power and current readings of the
selected outlet in the Manual Mode on an inline monitor. To enter the
Manual Mode, press the Up or Down button.
To operate the LED display of an inline monitor:
1. Press the Up or Down button until the desired outlet number is
selected in the two-digit row.
Pressing the Up button moves up one selection.
Pressing the Down button moves down one selection.
2. Current of the selected outlet is shown in the three-digit row. It
appears in this format: XX.X (A).
3. If desired, you can press the Up and Down buttons simultaneously to
switch between current and voltage readings.
The voltage appears in this format: XXX (V). It is displayed for
about five seconds, after which the current reading re-appears.
4. To switch to the active power readings, press the Up or Down button
until the unbalanced load is selected in the two-digit row, such as 1U.
Then press Up and Down buttons simultaneously to switch to the
active power mode, such as 1P. Now you can press the Up or Down
button to switch between the active power of different outlets/inlets.
The active power appears in this format: X.XX (W). It is displayed
for about five seconds, after which the current reading re-appears.
To exit from the active power mode, do NOT press any button until the
LED display returns to the Automatic Mode.
Note: The LED display returns to the Automatic Mode after 10 seconds
elapse since the last time any button was pressed.
Tip: A quick way to distinguish between voltage, current, and power is the
placement of the decimal point in the display. Voltage has no decimal
point, active power has a decimal point between the first and second
digits, and current has a decimal point between the second and third
digits.
Inline Monitor's Web Interface
An inline monitor's web interface is similar to a regular Dominion PX
model's web interface.
See
Using the Web Interface
(on page 39) for login instructions and
additional information.