Chapter 5: Introduction to PDU Components
119
3.
Press the ON button until it is completely down.
Resetting the Handle-Type Circuit Breaker
Your handle-type circuit breakers may look slightly different from the
images shown in this section, but the reset procedure remains the same.
To reset the handle-type breakers:
1.
Lift the hinged cover over the breaker.
2.
Check if the colorful rectangle or triangle below the operating
handle is GREEN, indicating that the breaker has tripped.
3.
Examine your PX3 and the connected equipment to remove or
resolve the cause that results in the overload or short circuit. This
step is required, or you cannot proceed with the next step.
4.
Pull up the operating handle until the colorful rectangle or triangle
turns RED.