Chapter 6: Using the Web Interface
138
Left side - generic inlet power data:
The left side lists all or some of the following data. Available data is
model dependent.
Active power (kW or W)
Apparent power (kVA or VA)
Active energy (kWh or Wh)
Power factor
Line frequency (Hz) -
model dependent
Unbalanced current (%) -
model dependent
Right side - inlet's current and voltage:
The right side shows the current and voltage data per phase. For a
single-phase device, it shows only one line, but for a three-phase device,
it shows three lines (L1, L2 and L3).
Inlet data from top to bottom includes:
RMS current (A)
A bar showing the RMS current level
RMS voltage (V)
The RMS current bars automatically change colors to indicate the
current status if the thresholds have been enabled. To configure
thresholds, see
Inlet
(on page 155).
Status
Bar colors
normal
above upper warning
above upper critical
Note: The "below lower warning" and "below lower critical" states also
show yellow and red colors respectively. However, it is not meaningful to
enable these two thresholds for current levels.