Appendix F: PX3 Models with Residual Current Monitoring
601
config:#
residualCurrentMonitor <n> warningRatedResidualOperatingCurrent <value>
To configure the RCM's deassertion hysteresis:
config:#
residualCurrentMonitor <n> deassertionHysteresis <hy_value>
Variables:
<n> is the number of the inlet where the desired RCM current sensor
is mounted. For a single-inlet PDU, this number is always 1.
<value> is one of the options:
enable, disable or a numeric value
measured in amperes.
Option
Description
enable
Enables the specified RCM current threshold for
the specified inlet.
disable
Disables the specified RCM current threshold for
the specified inlet.
A numeric
value
Sets a value for the specified RCM current
threshold of the specified inlet and enables this
threshold simultaneously.
Note that this value is measured in A, not mA.
Therefore, to set the value to 6mA, type
0.006.
<hy_value> is a numeric value measured in amperes (A), not
milliamperes (mA). For example, to set the value to 15mA, type
0.015.
Setting Front Panel RCM Self-Test
You can enable or disable the front panel RCM self-test function via CLI
in addition to the web interface.
To enable the front panel RCM self-test:
#
security frontPanelPermissions add rcmSelfTest
To disable the front panel RCM self-test:
#
security frontPanelPermissions remove rcmSelfTest
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...