Chapter 8: Using the Command Line Interface
412
Enabling or Disabling Peripheral Device Auto Management
This command enables or disables the Peripheral Device Auto
Management feature.
config:#
pdu peripheralDeviceAutoManagement <option>
Variables:
<option> is one of the options:
enable or disable.
Option
Description
enable
Enables the automatic management feature for
environmental sensor packages.
disable Disables
the
automatic management feature for
environmental sensor packages.
For more information, see
How the Automatic Management Function
Works
(on page 152).
Examples
This section illustrates several PDU configuration examples.
Example 1 - PDU Naming
The following command assigns the name "my px12" to the PDU.
config:#
pdu name "my px12"
Example 2 - Outlet Sequence
The following command causes a 10-outlet PDU to first power on the 8th
to 6th outlets and then the rest of outlets in the ascending order after the
PDU powers up.
config:#
pdu outletSequence 8-6,1-5,9,10
Example 3 - Outlet Sequence Delay
The following command determines that the outlet 1's delay is 2.5
seconds, outlet 2's delay is 3 seconds, and the delay for outlets 3 through
5 is 10 seconds.
config:#
pdu outletSequenceDelay 1:2.5;2:3;3-5:10
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...