Chapter 8: Using the Command Line Interface
521
Multi-Command Syntax
To shorten the configuration time, you can combine various configuration
commands in one command to perform all of them at a time. All
combined commands must belong to the same configuration type, such
as commands prefixed with
network, user modify, sensor externalsensor
and so on.
A multi-command syntax looks like this:
<configuration type> <setting 1> <value 1> <setting 2>
<value 2> <setting 3> <value 3> ...
Example 1 - Combination of IP, Subnet Mask and Gateway Parameters
The following multi-command syntax configures IPv4 address, subnet
mask and gateway for the network connectivity simultaneously.
config:#
network ipv4 ipAddress 192.168.84.225 subnetMask 255.255.255.0
gateway 192.168.84.0
Results:
The IP address is set to 192.168.84.225.
The subnet mask is set to 255.255.255.0.
The gateway is set to 192.168.84.0.
Example 2 - Combination of Upper Critical and Upper Warning Settings
The following multi-command syntax simultaneously configures Upper
Critical and Upper Warning thresholds for the RMS current of the 2nd
overcurrent protector.
config:#
sensor ocp 2 current upperCritical disable upperWarning 15
Results:
The Upper Critical threshold of the 2nd overcurrent protector's RMS
current is disabled.
The Upper Warning threshold of the 2nd overcurrent protector's
RMS current is set to 15A and enabled at the same time.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...