Chapter 8: Using the Command Line Interface
527
If you entered the command without "/y", a message appears, prompting
you to confirm the operation. Then:
Type
y
to confirm the operation, OR
Type
n
to abort the operation
Canceling the Power-On Process
This section applies to outlet-switching capable models only.
After issuing the command to power on ALL outlets, you can use the
following command to stop the power-on process.
#
power cancelSequence
To quicken the operation, you can add the parameter "/y" to the end of
the command, which confirms the operation.
#
power cancelSequence /y
Example - Power Cycling Specific Outlets
The following command power cycles these outlets: 2, 6, 7, 8, 10, 13, 14,
15 and 16.
#
power outlets 2,6-8,10,13-16 cycle
Actuator Control Operations
An actuator, which is connected to a dry contact signal channel of a DX
sensor, can control a mechanism or system. You can switch on or off that
mechanism or system through the actuator control command in the CLI.
Perform these commands in the administrator or user mode. See
Different CLI Modes and Prompts
(on page 368).