Appendix F: PX3 Models with Residual Current Monitoring
591
Compliance with IEC 62020
IEC 62020 is an international standard for Residual Current Monitors. All
PX3 with RCM are IEC 62020 compliant.
IEC 62020 uses the term
rated residual operating current (IΔn) to specify
residual current, equal to or above which causes an alarm. IEC 62020
recommends preferred values 6mA, 10mA, 30mA, 100mA, 300mA and
500mA. In the PX3 with RCM, IΔn is specified using the Critical Rated
Residual Operating Current threshold.
Note: The PX3 triggers events when residual current values are above
(but not equal to) thresholds. For example, you would set the critical
threshold to 29mA to specify the IEC 62020 IΔn of 30mA.
IEC 62020 uses the term
residual non-operating current (IΔno) to specify
residual current, below which does not cause an alarm. IEC 62020
specifies IΔno be no higher than 0.5 IΔn. In PX3 with RCM, IΔno is set
using the RCM Deassertion Hysteresis and this value must be no higher
than 0.5 the RCM critical threshold.
PX3 with RCM allows you to establish an optional WARNING state, which
is not part of the IEC 62020 specification. PX3 RCM remains IEC 62020
compliant when the RCM deassertion hysteresis is configured properly.
IEC 62020 specification
PX3 with RCM characteristics
Method of operation
Dependent on line voltage. RCM only functions if
line voltage is present.
Type of installation
PX3 with flexible line cords and plugs are for
mobile installation and corded connection.
Current paths
1-phase PX3 are two current paths RCM.
3-phase 3W+PE are three current paths RCM.
3-phase 4W+PE are four current paths RCM.
Ability to adjust residual
operating current
Adjustable.
Type A: 6mA-500mA.
Type B: 30mA-500mA.
Adjustable time delay
Non-adjustable time delay.
Protection against external
influence
Enclosed-type RCM.
Method of mounting
Panel board type RCM.
Method of connection
Not associated with mechanical mounting.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...