Appendix F: PX3 Models with Residual Current Monitoring
593
RCM State: There are five states - normal, warning, critical,
self-test active and failure. For more information, see
RCM
State Sensor
(on page 589).
Residual Operating Current: The magnitude of residual current
detected.
Note: To determine the RCM's normal, warning and critical levels,
configure the RCM current thresholds. See
Setting RCM Current
Thresholds
(on page 592).
RCM Critical State Alarm
When a PX3 device's RCM enters the Critical state, the PX3 beeps and
this alarm is displayed in the Alerted Sensors section of the Dashboard
page.
Number
Description
The magnitude of residual current reported by the RCM
current sensor.
Critical state reported by the RCM state sensor.
Tip: RCM critical state is also indicated on the Inlet page or the Internal
Beeper section of the PDU page. See
Checking RCM State and Current
(on page 591) or
Internal Beeper State
(on page 148).
Setting RCM Current Thresholds
The RCM current thresholds define the critical, warning and normal
range of residual current.
To configure the RCM current thresholds and run self-test:
1.
Click Inlet to open the Inlet page.
2.
In the Residual Current Monitor section, click Setup.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...