Chapter 8: Using the Command Line Interface
465
Displayed information:
Without the parameter "details," only the reading, state, threshold,
deassertion hysteresis and assertion timeout settings of the
specified inlet sensor are displayed.
With the parameter "details," more sensor information is displayed,
including resolution and range.
If the requested sensor type is not supported, the "Sensor is not
available" message is displayed.
Inlet Pole Sensor Threshold Information
This command is only available for a three-phase PDU except for an
in-line monitor (PX-3000 series).
This command syntax shows the specified inlet pole sensor's
threshold-related information.
#
show sensor inletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of
the command.
#
show sensor inletpole <n> <p> <sensor type>
details
Variables:
<n> is the number of the inlet whose pole sensors you want to query.
For a single-inlet PDU, <n> is always the number 1.
<p> is the label of the inlet pole whose sensors you want to query.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
Summary of Contents for PX3-3000 series
Page 5: ......
Page 18: ...Contents xviii Index 841...
Page 93: ...Chapter 4 Connecting External Equipment Optional 69...
Page 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Page 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Page 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Page 823: ...Appendix K Additional PX3 Information 799...