Chapter 6: Using the Web Interface
143
6. If selecting Port Forwarding, a list of port numbers for diverse
networking protocols will be available on the "Protocol to Port
Mapping" tab of each cascaded device.
Return to the same dialog and click the "Protocol to Port Mapping"
tab to view the master device's port numbers.
For information on accessing each cascaded device in the Port
Forwarding mode, see
Port Forwarding Examples
(on page 145).
Port Number Syntax
In the Port Forwarding mode, all devices in the USB-cascading
configuration share the same IP address. To access any cascaded
device, you must assign an appropriate port number to it.
Master device: The port number is either
5NNXX
or the standard
TCP/UDP port.
Slave device: The port number is
5NNXX
.
5NNXX port number syntax:
NN is a two-digit number representing the network protocol as shown
below:
Protocols
NN
HTTPS
00
HTTP
01
SSH
02