Chapter 6: Using the Web Interface
215
6. If disabling an inlet will result in all inlets being disabled, a
confirmation dialog appears, indicating that all inlets will be disabled.
Then click Yes to confirm this operation or No to abort it.
Setting Power Thresholds
Setting and enabling the thresholds causes the PX to generate alert
notifications when it detects that any component's power state crosses
the thresholds. See
The Yellow- or Red-Highlighted Sensors
(on page
105).
There are four thresholds for each sensor: Lower Critical, Lower Warning,
Upper Warning and Upper Critical.
Upper and Lower Warning thresholds indicate the sensor reading
enters the warning level.
Upper and Lower Critical thresholds indicate the sensor reading
enters the critical level.
To avoid generating a large amount of alert events, you can set the
assertion timeout and deassertion hysteresis.
For detailed information, see
Sensor Threshold Settings
(on page
648).
Note: After setting the thresholds, remember to configure event rules.
See
Event Rules and Actions
(on page 222).
Setting an Outlet's Thresholds
You can set up the thresholds, deassertion hysteresis and assertion
timeout for a particular outlet.
The threshold values set for an individual outlet will override the bulk
threshold values stored on that outlet. See
Bulk Configuration for
Outlet Thresholds
(on page 216).
To set the thresholds for an outlet:
1. Expand the Outlets folder in the PX Explorer pane to show all outlets.
See
Expanding the Tree
(on page 100).
2. In the PX Explorer pane, click the outlet you want. The page specific
to that outlet opens in the right pane.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...