Chapter 6: Using the Web Interface
219
3. Click Setup. The Overcurrent Protector Setup dialog appears.
4. In the Threshold Configuration table, click the sensor whose
thresholds you want to configure.
5. Click Edit or double-click the desired sensor. A threshold setup
dialog appears.
6. Configure the Lower Critical, Lower Warning, Upper Warning and
Upper Critical thresholds respectively.
To enable any threshold, select the corresponding checkbox. To
disable a threshold, deselect the checkbox.
After any threshold is enabled, type an appropriate numeric value
in the accompanying text box.
7. To set the deassertion hysteresis, type a numeric value in the
Deassertion Hysteresis field. See
"To De-assert" and Deassertion
Hysteresis
(on page 653).
8. To set the assertion timeout, type a numeric value in the Assertion
Timeout (samples) field. See
"To Assert" and Assertion Timeout
(on page 651).
9. Click OK.
Bulk Configuration for Overcurrent Protector Thresholds
The PX allows you to set power thresholds for multiple overcurrent
protectors at a time to save your time.
Note: To set the power thresholds for an individual overcurrent protector,
you can either follow the instructions below or those described in the
section
Setting an Overcurrent Protector's Thresholds
(on page 218).
To configure thresholds, deassertion hysteresis and assertion
timeout for multiple overcurrent protectors:
1. Click the Overcurrent Protectors folder in the PX EXplorer pane. The
Overcurrent Protectors page opens.
2. Click Bulk Setup. The Overcurrent Protector Threshold Bulk Setup
dialog appears, with a list of all overcurrent protectors.
3. Select desired overcurrent protectors by having their corresponding
checkboxes selected.
To select all overcurrent protectors, select the checkbox labeled
Sensor in the header row, and all checkboxes are selected.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...