Chapter 6: Using the Web Interface
220
To select partial overcurrent protectors, click the corresponding
checkboxes of those overcurrent protectors.
To deselect any overcurrent protectors, just click their
checkboxes once again.
4. Click Edit Thresholds. The threshold bulk setup dialog appears.
5. Configure the Lower Critical, Lower Warning, Upper Warning and
Upper Critical thresholds respectively.
To enable any threshold, select the corresponding checkbox. To
disable a threshold, deselect the checkbox.
After any threshold is enabled, type an appropriate numeric value
in the accompanying text box.
6. To set the deassertion hysteresis, type a numeric value in the
Deassertion Hysteresis field. See
"To De-assert" and Deassertion
Hysteresis
(on page 653).
7. To set the assertion timeout, type a numeric value in the Assertion
Timeout (samples) field. See
"To Assert" and Assertion Timeout
(on page 651).
8. Click OK.
Setting Thresholds for Total Active Energy or Power
This section applies only to multi-inlet models, including PX in-line
monitors.
Thresholds for total active energy and total active power are disabled by
default. You can enable and set them so that you are alerted when the
total active energy or total active power hits a certain level.
For a regular PX model with multiple inlets:
Total active energy = sum of all inlets' active energy values
Total active power = sum of all inlets' active power values
For an in-line monitor with multiple inlets/outlets:
Total active energy = sum of all outlets' active energy values
Total active power = sum of all outlets' active power values
Tip: You can reset the active energy sensor(s) as needed. See
Resetting All Active Energy Readings
(on page 151).
To set thresholds for total active energy and/or power on a
multi-inlet PX:
1. Click the PDU folder.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...