Chapter 6: Using the Web Interface
233
a. In the Timeout (sec) field, enter the interval of time, in seconds,
after which a new inform communication is resent if the first is
not received. For example, resend a new inform communication
once every 3 seconds.
b. In the Number of Retries field, enter the number of times you
want to resend the inform communication if it fails. For example,
inform communications are resent up to 5 times when the initial
communication fails.
3. In the Host fields, enter the IP address of the device(s) you want to
access. This is the address to which notifications are sent by the
SNMP system agent.
4. In the Port fields, enter the port number used to access the
device(s).
5. In the Community fields, enter the SNMP community string to access
the device(s). The community is the group representing the PX and
all SNMP management stations.
Tip: An SNMP v2c notification action only permits entering a maximum of
three SNMP destinations. To assign more than three SNMP destinations
to a specific rule, first create several SNMP v2c notification actions, each
of which contains completely different SNMP destinations, and then add
all of these SNMP v2c notification actions to the same rule.
To send SNMP v3 notifications:
1. From the Notification Type drop-down, select SNMPv3 Trap or
SNMPv3 Inform.
2. For SNMP TRAPs, the engine ID is prepopulated.
3. For SNMP INFORM communications, leave the resend settings at
their default or:
a. In the Timeout (sec) field, enter the interval of time, in seconds,
after which a new inform communication is resent if the first is
not received. For example, resend a new inform communication
once every 3 seconds.
b. In the Number of Retries field, enter the number of times you
want to resend the inform communication if it fails. For example,
inform communications are resent up to 5 times when the initial
communication fails.
4. For both SNMP TRAPS and INFORMS, enter the following as
needed and then click OK to apply the settings:
a. Host name
b. Port number
c. User ID needed to access the host
d. Select the host security level
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...