Chapter 6: Using the Web Interface
264
For example, when the Inlet I1's voltage enters the upper warning
range, the SNMP notifications are sent, and when the voltage drops
below the upper warning threshold, returning to the normal state, the
SNMP notifications are sent again.
Sample Environmental-Sensor-Level Event Rule
This section applies to outlet-switching capable models only.
In this example, we want PX to enable the load shedding function when
a contact closure sensor enters the alarmed state. This sample event
rule requires creating a new action before creating the rule.
Step 1: create a new action for enabling the load shedding
mode
1. Choose Device Settings > Event Rules. The Event Rule Settings
dialog appears.
2. Click the Actions tab.
3. Click New Action.
4. In the Action Name field, type a name to identify this action. In this
illustration, type Activate Load Shedding.
5. In the Action field, select "Change load shedding state."
6. In the Operation field, select Start Load Shedding.
7. Click Save to save this action.
After the new action for enabling the load shedding mode is created, you
can create an event rule that can trigger the load shedding mode when
the contact closure sensor enters the alarmed state. This sample event
rule looks like this:
Event: Peripheral Device Slot > Slot 1 > State Sensor >
Alarmed/Open/On
Trigger condition: Alarmed/Open/On
Actions: Activate Load Shedding
Step 2: create the contact closure triggered load shedding event
rule
1. Click the Rules tab.
2. Click New Rule.
3. In the "Rule name" field, type a name to identify this event rule. In
this illustration, type Contact Closure Triggered Load Shedding.
4. Select the Enabled checkbox. Otherwise, the new event rule will not
be carried out.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...