Chapter 8: Using the Command Line Interface
360
Outlet Pole Sensor Threshold Information
This command is available for an in-line monitor only, including
PX2-3000 and PX3-3000 series.
This command syntax shows the specified outlet pole sensor's
threshold-related information.
#
show sensor outletpole <n> <p> <sensor type>
To show detailed information, add the parameter "details" to the end of
the command.
#
show sensor outletpole <n> <p> <sensor type>
details
Variables:
<n> is the number of the outlet whose pole sensors you want to
query.
<p> is the label of the outlet pole whose sensors you want to query.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current
Current sensor
voltage
Voltage sensor
activePower
Active power sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...