Chapter 8: Using the Command Line Interface
381
Setting the Outlet Power-On Sequence
This section applies to outlet-switching capable models only.
This command sets the outlet power-on sequence when the PDU powers
up.
config:#
pdu outletSequence <option>
Variables:
<option> is one of the options:
default
, or a comma-separated list of
outlet numbers.
Option
Description
default
All outlets are switched ON in the ASCENDING
order (from outlet 1 to the final outlet) when the
PX device powers up.
A comma-
separated list of
outlet numbers
All outlets are switched ON in the order you
specify using the comma-separated list.
The list must include all outlets on the PDU.
Note: Power-on sequencing is disabled in the latching mode. See
PX3
Latching Relay Behavior
(on page 192).
Setting the Outlet Power-On Sequence Delay
This section applies to outlet-switching capable models only.
This command sets the delays (in seconds) for outlets when turning on
all outlets in sequence.