Chapter 8: Using the Command Line Interface
383
Note: This feature does NOT take effect and cannot be configured on a
PX3 device after the outlet relay is set to the "Latching" mode. See
Setting the Outlet Relay Behavior
(on page 193).
Setting the PDU-Defined Cycling Power-Off Period
This section applies to outlet-switching capable models only.
This command sets the power-off period of the power cycling operation
for all outlets.
config:#
pdu cyclingPowerOffPeriod <timing>
Variables:
<timing> is the time of the cycling power-off period in seconds, which
is an integer between 0 and 3600, or
pduDefined
for following the
PDU-defined timing.
Setting the Inrush Guard Delay Time
This section applies to outlet-switching capable models only.
This command sets the inrush guard delay.
config:#
pdu inrushGuardDelay <timing>
Variables:
<timing> is a delay time between 100 and 100000 milliseconds.
Summary of Contents for PX3-4000 series