Chapter 8: Using the Command Line Interface
466
Option
Description
A numeric
value
Sets a value for the specified threshold of a
specific outlet sensor and enables this threshold
at the same time.
<hy_value> is a numeric value that is assigned to the hysteresis for
the specified outlet sensor. See
"To De-assert" and Deassertion
Hysteresis
(on page 653).
<as_value> is a number in samples that is assigned to the assertion
timeout for the specified outlet sensor. See
"To Assert" and
Assertion Timeout
(on page 651).
Commands for Inlet Sensors
A sensor configuration command for inlets begins with
sensor inlet
.
You can configure various inlet sensor threshold settings at a time by
combining multiple commands. See
Multi-Command Syntax
(on page
491).
Set the Upper Critical threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an inlet sensor:
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...