Chapter 8: Using the Command Line Interface
473
Option
Description
A numeric
value
Sets a value for the specified threshold of a
specific environmental sensor and enables this
threshold at the same time.
<hy_value> is a numeric value that is assigned to the hysteresis for
the specified environmental sensor. See
"To De-assert" and
Deassertion Hysteresis
(on page 653).
<as_value> is a number in samples that is assigned to the assertion
timeout for the specified environmental sensor. It ranges between 1
and 100. See
"To Assert" and Assertion Timeout
(on page 651).
Examples
This section illustrates several environmental sensor threshold
configuration examples.
Example 2 - Warning Thresholds for Inlet Sensors
The following command sets both the Upper Warning and Lower
Warning thresholds for the inlet 1 RMS current.
config:#
sensor inlet 1 current upperWarning 20 lowerWarning 12
Results:
The Upper Warning threshold for the inlet 1 RMS current is set to
20A. It also enables the upper warning threshold if this threshold has
not been enabled yet.
The Lower Warning threshold for the inlet 1 RMS current is set to
12A. It also enables the lower warning threshold if this threshold has
not been enabled yet.
Example 1 - Upper Critical Threshold for a Temperature Sensor
The following command sets the Upper Critical threshold of the
environmental "temperature" sensor with the ID number 2 to 40 degrees
Celsius. It also enables the upper critical threshold if this threshold has
not been enabled yet.
config:#
sensor externalsensor 2 temperature upperCritical 40
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning
thresholds for the 2nd overcurrent protector.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...