Chapter 8: Using the Command Line Interface
492
Example 3 - Combination of SSID and PSK Parameters
This multi-command syntax configures both SSID and PSK parameters
simultaneously for the wireless feature.
config:#
network wireless SSID myssid PSK encryp_key
Results:
The SSID value is set to myssid.
The PSK value is set to encryp_key.
Example 4 - Combination of Upper Critical, Upper Warning and Lower
Warning Settings
The following multi-command syntax configures Upper Critical, Upper
Warning and Lower Warning thresholds for the outlet 5 RMS current
simultaneously.
config:#
sensor outlet 5 current upperCritical disable upperWarning enable
lowerWarning 1.0
Results:
The Upper Critical threshold of outlet 5 RMS current is disabled.
The Upper Warning threshold of outlet 5 RMS current is enabled.
The Lower Warning threshold of outlet 5 RMS current is set to 1.0A
and enabled at the same time.
Load Shedding Configuration Commands
This section applies to outlet-switching capable models only.
A load shedding configuration command begins with
loadshedding
.
Unlike other CLI configuration commands, the load shedding
configuration command is performed in the
administrator mode
rather
than the configuration mode. See
Different CLI Modes and Prompts
(on page 345).
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...