507
The model name of a PX in-line monitor follows this format: PX3-3nnn,
where n is a number, such as PX3-3411.
Unlike most of PX devices, each inlet of an in-line monitor is connected
to an outlet only, so an inlet's rating is the same as an outlet's rating.
In This Chapter
Overview................................................................................................507
Safety Instructions .................................................................................507
Flexible Cord Installation Instructions....................................................508
In-Line Monitor's Web Interface.............................................................516
Overview
An in-line monitor is implemented with the same number of inlets and
outlets. An inlet is connected to a power source for receiving electricity,
such as electric distribution panels or branch circuit receptacles. An
outlet is connected to a device that draws power, such as a cooling or IT
device.
Inlets are located at the side labeled
Line
, and outlets are located at the
side labeled
Load
.
Safety Instructions
1. Installation of this product should only be performed by a licensed
electrician.
2. Make sure the line cord is disconnected from power before physically
mounting or moving the location of this product.
3. This product is intended to be located in an equipment rack in an
information technology room. In the United States, installation must
comply and be done in accordance with NEC (2011) Article 645
Information Technology Equipment
.
4. This product is designed to be used within an electronic equipment
rack. The metal case of this product is electrically bonded to the line
cord ground wire. A threaded grounding point on the case may be
used as an additional means of protectively grounding this product
and the rack.
5. Examine the branch circuit receptacle that will supply electric power
to this product. Make sure the receptacle’s power lines, neutral and
protective earth ground pins are wired correctly and are the correct
voltage and phase. Make sure the branch circuit receptacle is
protected by a suitably rated fuse or circuit breaker.
Chapter 9
In-Line Monitors
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...