Chapter 9: In-Line Monitors
515
If your PDU is inlet metered, such as PDU models PX2-1nnn and
PX2-2nnn (where n is a number), you must pass each line cord
wire through the correct CT in the correct direction. Each CT is
labeled and contains a direction arrow. Push the ring terminal
end of the line cord through the CT in the direction indicated by
the arrow. For example, push the L1 line cord wire through the
CT labeled L1 and then connect it to the L1 terminal block.
For Raritan in-line monitors, where there is a one to one
correspondence between plug and receptacle, maintain the
same wire colors for inlet and outlet flexible cords.
7. Make final adjustments to the cable gland and verify the jacket of the
flexible cord extends into the Raritan product. Hand tighten the gland
nut and finish tightening with a torque wrench. Appropriate torque
settings vary according to the cable gland size.
Cable gland size
Torque setting (N·m)
M12x1.5
0.7 to 0.9
M16x1.5
2.0 to 3.0
M20x1.5
2.7 to 4.0
M25x1.5
5.0 to 7.5
M32x1.5
7.5 to 10.0
M40x1.5
7.5 to 10.0
M50x1.5
7.5 to 10.0
M63x1.5
7.5 to 10.0
Note: The cable gland size is marked on the cable gland body.
After tightening, examine the flexible cord and cable gland for the
following:
Make sure you can see a few remaining threads between the
cable gland body and cable gland nut. The gland nut must not
bottom out on the gland body.
Make sure the flexible cord does not move in the cable gland
when it is twisted, pushed or pulled.
8. Re-install the PDU wiring access panel or in-line monitor cover plate.
This completes internal wiring of the Raritan product.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...