Appendix G: PX Models with Residual Current Monitoring
581
Running RCM Self-Test
You can perform the RCM self-test by operating the front panel buttons.
To disable or enable this front panel function, see
Disabling or
Enabling Front Panel RCM Self-Test
(on page 577). By default, this
function is enabled.
Follow the RCM self-test procedures below according to your model
type.
PX3 phase II models:
1. Press
or
to access the
Main Menu
(on page 63).
2. Press
or
to select "Residual Current," and press
.
3. The LCD display shows the RCM information for the inlet(s).
4. Press
to perform RCM self-test on the selected inlet.
If your PDU has multiple inlets, press
or
to select the
desired inlet and press
.
5. A confirmation message displays. By default, Yes is selected.
To execute the RCM self-test, press
.
To cancel the RCM self-test, do either of the following:
- Press
.
- Press
or
to select No and then press
.