Appendix G: PX Models with Residual Current Monitoring
583
Below illustrates the RCM self-test mode.
Section
Example information
The inlet containing RCM sensor is INLET 1.
The LCD alternates between "SLF" and "tSt" to indicate
that this is self-test mode.
ALARM
always displays for residual current sensor.
LEAK
always displays for residual current sensor.
RCM SNMP Operations
Make sure you have the correct version of SNMP MIB. The PX supports
the RCM feature as of firmware version 2.5.20. See
Downloading
SNMP MIB
(on page 337) for details.
RCM Trap
An
InletSensorStateChange
trap is sent when the RCM state sensor
changes.
InletSensorStateChange
is the generic trap sent for all inlet
sensors. The specific trap for RCM has the object
typeOfSensor
set to
27. Included with the trap are
measurementsInletSensorValue
(the
residual current value) and
measurementsInletSensorState
(the RCM
state that caused the trap).
RCM Residual Current and State Objects
The
inletSensorMeasurementsTable
contains entries for RCM residual
current and states.
Use index
sensorType
= 26 to retrieve the row for residual current.
Column
measurementsInletSensorValue
contains the residual current.
Use index
sensorType
= 27 to retrieve the row for RCM state. Column
measurementsInletSensorState
contains the RCM state enumeration
value.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...