Chapter 4: Connecting External Equipment (Optional)
40
DX Sensor Packages
Most DX sensor packages contain terminals for connecting detectors or
actuators. For information on connecting actuators or detectors to DX
terminals, access the Environmental Sensors Guide or Online Help on
Raritan website's
PX2 Support Files page
(
https://www.raritan.com/support/product/px2/px2-support-files
).
You can cascade up to 12 DX sensor packages.
When cascading DX, remember that the PX only supports a maximum of
32 sensors or actuators.
If there are more than 32 sensors and/or actuators connected, every
sensor and/or actuator after the 32nd one is ignored by PX.
For example, if you cascade 12 DX packages, and each package
contains 3 functions (a function is a sensor or actuator), PX ignores the
last 4 functions because the total 36 (12*3=36) exceeds 32 by 4.
Tip: To manage the last 4 functions, you can release 4 sensors or
actuators that have been under management, and then manually bring
the last 4 functions into management. See
Unmanaging Environmental
Sensors or Actuators
(on page 293) and
Managing Environmental
Sensors or Actuators
(on page 281).
Numbers Components
RJ-45 ports, each of which is located on
either end of a DX sensor package.
RJ-12 port, which is reserved for future use
and is now hidden.
Removable rackmount brackets.
Connect DX sensor packages to the PX:
1. Connect a standard network patch cable (CAT5e or higher) to either
RJ-45 port on a DX sensor package.
2. If you want to cascade DX packages, get an additional standard
network patch cable (CAT5e or higher) and then:
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...