5. In the Community fields, enter the SNMP community string to access
the device(s). The community is the group representing the PXE and
all SNMP management stations.
Tip: An SNMP v2c notification action only permits entering a maximum of
three SNMP destinations. To assign more than three SNMP destinations
to a specific rule, first create several SNMP v2c notification actions, each
of which contains completely different SNMP destinations, and then add
all of these SNMP v2c notification actions to the same rule.
To send SNMP v3 notifications:
1. From the Notification Type drop-down, select SNMPv3 Trap or
SNMPv3 Inform.
2. For SNMP TRAPs, the engine ID is prepopulated.
3. For SNMP INFORM communications, leave the resend settings at
their default or:
a. In the Timeout (sec) field, enter the interval of time, in seconds,
after which a new inform communication is resent if the first is
not received. For example, resend a new inform communication
once every 3 seconds.
b. In the Number of Retries field, enter the number of times you
want to resend the inform communication if it fails. For example,
inform communications are resent up to 5 times when the initial
communication fails.
4. For both SNMP TRAPS and INFORMS, enter the following as
needed and then click OK to apply the settings: