Chapter 6: Using the Web Interface
131
Send Sensor Report
You may set the PXE so that it automatically reports the latest readings
or states of one or multiple sensors by sending a message or email or
simply recording the report in a log. These sensors can be either internal
or environmental sensors as listed below.
Inlet sensors, including RMS current, RMS voltage, active power,
apparent power, power factor and active energy.
Outlet sensors, including RMS current, RMS voltage, active power,
apparent power, power factor, active energy and outlet state (for
outlet-switching capable PDUs only).
Overcurrent protector sensors, including RMS current and tripping
state.
Peripheral device sensors, which can be any Raritan environmental
sensor packages connected to the PXE, such as temperature or
humidity sensors.
To configure a sensor report action:
1. Choose Device Settings > Event Rules. The Event Rules Settings
dialog opens.
2. Click the Actions tab.
3. Click
New.
4. In the "Action name" field, type a new name for the action. The
default name is New Action <number>, where <number> is a
sequential number starting at 1.
5. In the Action field, click the drop-down arrow and select the desired
action: Send Sensor Report.
6. In the Destination Actions field, select the method(s) to report sensor
readings or states. The number of available methods vary,
depending on how many messaging actions have been created.
The messaging action types include:
Log event message
Syslog
message
Send SMTP message
Send SMS message
a. If no messaging actions are available, click Create New
Destination Action to immediately create them.
b. To select any method, select it in the right list box, and click
to move it to the left list box. To make multiple selections, press
Ctrl+click or Shift+click to highlight multiple ones.