Chapter 8: Using the Command Line Interface
288
Example 1 - Environmental Sensor Naming
The following command assigns the name "Cabinet humidity" to the
environmental sensor with the ID number 4.
config:#
externalsensor 4 name "Cabinet humidity"
Example 2 - Sensor Threshold Selection
The following command sets the environmental sensor #1 to use the
default thresholds, including the deassertion hysteresis and assertion
timeout, as its threshold settings.
config:#
externalsensor 1 useDefaultThresholds true
Sensor Threshold Configuration Commands
A sensor configuration command begins with
sensor
. You can use the
commands to configure the threshold, hysteresis and assertion timeout
values for any sensor associated with the following items:
Inlets
Inlet poles (for three-phase PDUs only)
Overcurrent
protectors
Environmental
sensors
It is permitted to assign a new value to the threshold at any time
regardless of whether the threshold has been enabled.
Commands for Inlet Sensors
A sensor configuration command for inlets begins with
sensor inlet
.