Chapter 8: Using the Command Line Interface
297
Option
Description
A numeric
value
Sets a value for the upper warning threshold of
the specified inlet pole sensor and enables this
threshold at the same time.
Setting the Lower Critical Threshold for an Inlet Pole
This command syntax configures the Lower Critical threshold of an inlet
pole.
config:#
sensor inletpole <n> <p> <sensor type> lowerCritical <option>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Note: If the requested sensor type is not supported, the "Sensor is
not available" message is displayed.