Chapter 8: Using the Command Line Interface
306
Examples
This section illustrates several environmental sensor threshold
configuration examples.
Example 1 - Warning Thresholds for Inlet Sensors
The following command sets both the Upper Warning and Lower
Warning thresholds for the inlet 1 RMS current.
config:#
sensor inlet 1 current upperWarning 20 lowerWarning 12
Results:
The Upper Warning threshold for the inlet 1 RMS current is set to
20A. It also enables the upper warning threshold if this threshold has
not been enabled yet.
The Lower Warning threshold for the inlet 1 RMS current is set to
12A. It also enables the lower warning threshold if this threshold has
not been enabled yet.
Example 2 - Upper Critical Threshold for a Temperature Sensor
The following command sets the Upper Critical threshold of the
environmental "temperature" sensor with the ID number 2 to 40 degrees
Celsius. It also enables the upper critical threshold if this threshold has
not been enabled yet.
config:#
sensor externalsensor 2 temperature upperCritical 40
Actuator Configuration Commands
An actuator configuration command begins with
actuator
. You can
configure the name and location parameters of an individual actuator.