Chapter 6: Using the Web Interface
147
Placeholder
Definition
[VERSION]
The firmware version the device is upgrading to
Sample Event Rules
Sample PDU-Level Event Rule
In this example, we want the PXE to record the firmware upgrade failure
in the internal log when it happens. The sample event rule looks like this:
Event: Device > Firmware update failed
Actions: System Event Log Action
To create the above event rule:
1. Select Event > Device to indicate we are specifying an event at the
PDU level.
2. Select "Firmware update failed" in the submenu because we want
the PXE to respond to the event related to firmware upgrade failure.
3. Select System Event Log Action as we intend to record the firmware
update failure event in the internal log.
Sample Inlet-Level Event Rule
In this example, we want the PXE to send SNMP notifications to the
SNMP manager for any sensor change event of the Inlet I1.
Note: The SNMP notifications may be SNMP v2c or SNMP v3 traps or
informs, depending on the settings for the System SNMP Notification
Action. See
Configuring SNMP Notifications
(on page 187).
The event rule is set like this:
Event: Inlet > Inlet I1 > Sensor > Any sub-event
Actions: System SNMP Notification Action
To create the above event rule:
1. Select Event > Inlet to indicate we are specifying an event at the inlet
level.
2. Select "Inlet I1" from the submenu because that is the inlet in
question.
3. Select "Sensor" to refer to sensor events.
4. Select "Any sub-event" because we want to specify all events related
to all types of inlet sensors and thresholds, such as current, voltage,
upper critical threshold, upper warning threshold, lower critical
threshold, lower warning threshold, and so on.