Chapter 8: Using the Command Line Interface
221
Setting Data Logging Measurements Per Entry
This command syntax defines the number of measurements
accumulated per log entry.
config:#
pdu measurementsPerLogEntry <number>
Variables:
<number> is an integer between 1 and 600. The default is 60
samples per log entry.
For more information, see
Setting Data Logging
Specifying the Device Altitude
This command syntax specifies your PXE device's altitude above sea
level (in meters). You must specify the PXE device's altitude above sea
level if a Raritan differential air pressure sensor is attached. This is
because the device's altitude is associated with the altitude correction
factor. See
Altitude Correction Factors
(on page 347).
config:#
pdu deviceAltitude <altitude>
Variables:
<altitude> is an integer between 1 and 3000 meters.
Setting the Z Coordinate Format for Environmental Sensors
This command syntax enables or disables the use of rack units for
specifying the height (Z coordinate) of environmental sensors.
config:#
pdu externalSensorsZCoordinateFormat <option>
Variables:
<option> is one of the options:
rackUnits
or
freeForm
.
Option
Description
rackUnits
The height of the Z coordinate is measured in
standard rack units. When this is selected, you
can type a numeric value in the rack unit to
describe the Z coordinate of any environmental
sensors or actuators.