Chapter 8: Using the Command Line Interface
286
Setting the Z Coordinate
This command syntax specifies the Z coordinate of an environmental
sensor.
config:#
externalsensor <n> zlabel "<coordinate>"
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PXE web interface or
using the show command in the CLI. It is an integer between 1 and
32.
Depending on the Z coordinate format you set, there are two types of
values for the <coordinate> variable:
Type
Description
Free form
<coordinate> is a string comprising up to 24
ASCII printable characters, and it must be
enclosed in quotes.
Rack units
<coordinate> is an integer number in rack units.
Note: To specify the Z coordinate using the rack units. See
Setting the Z
Coordinate Format for Environmental Sensors
Changing the Sensor Description
This command syntax provides a description for a specific environmental
sensor.
config:#
externalsensor <n> description "<description>"
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PXE web interface or
using the show command in the CLI. It is an integer between 1 and
32.
<description> is a string comprising up to 64 ASCII printable
characters, and it must be enclosed in quotes.