18
The PXE supports all types of Raritan environmental sensor packages,
including DPX, DPX2 and DX series. For detailed information on each
sensor package, download the Environmental Sensors Guide from
Raritan website's
PX2 Support Files page
(
The PXE supports a maximum of 32 sensors or actuators.
For information on connecting DPX packages, see
DPX Sensor
Packages
For information on connecting DPX2 packages, see
DPX2 Sensor
Packages
(on page 23).
For information on connecting DX packages, see
DX Sensor Packages
(on page 25).
In This Chapter
DPX Sensor Packages ............................................................................18
DPX2 Sensor Packages ..........................................................................23
DX Sensor Packages ..............................................................................25
DPX Sensor Packages
Most DPX sensor packages come with a factory-installed sensor cable,
whose sensor connector is RJ-12.
The supported maximum distance is 98 feet (30 m). See
Supported
Maximum DPX Sensor Distances
(on page 22) for further illustrations.
To connect a DPX sensor package with a factory-installed
sensor cable:
Plug the RJ-12 connector of the DPX sensor cable into the RJ-12
SENSOR port on the PXE.
To connect a DPX differential air pressure sensor:
1. Plug one end of a Raritan-provided phone cable into the IN port of a
differential air pressure sensor.
2. Plug the other end of this phone cable into the RJ-12 SENSOR port
on the PXE.