Chapter 4: Connecting Environmental Sensor Packages (Optional)
22
2. A Y cable has two RJ-12 sensor ports. Connect DPX sensor
packages to the Y cable's sensor ports.
3. Repeat the above steps if there are additional SENSOR ports on
your PXE.
Supported Maximum DPX Sensor Distances
A maximum connection distance of 98' (30 m) is supported when
connecting the following DPX packages to the PXE. This maximum
includes the 16' (5 m) sensor cable length:
DPX-CC2-TR
DPX-T1
DPX-T3H1
DPX-AF1
DPX-T1DP1
The following configurations were tested when connecting DPX sensor
packages to a PXE via a sensor hub:
PXE
16' (5 m)
cable
1 sensor hub
16' (5 m)
cable
Up to 4
DPX-T3H1
sensors