background image

VENT FREE OPERATION

PROVISIONS FOR ADEQUATE COMBUSTION AND VENTILATION AIR

This heater shall not be installed in a "confined" space or unusually tight construction unless provisions

are provided for adequate combustion and ventilation air.

Confined Or Unconfined Space Determination:

The National Fuel Gas Code defines a confined space as a space whose volume is less than 50 cubic feet per 1,000
Btu per hour (4.8m

3

 

per kW) of the aggregate input rating of all appliances installed in that space and an unconfined

space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8m

3

 per kW) of the aggregate

input rating of all appliances installed in that space. Rooms communicating directly with the space in which the
appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

Calculations To Determine Confined Or Unconfined Space:

1. Determine number of rooms (including adjoining rooms with doorless passageways or ventilation grates.)

Example: 

Living room/dining room + Kitchen

2. Determine the Total Volume of the Space (width x length x height).

Example: 

Living room/dining room

14' x 20' x  8' = 2240 cu ft

Kitchen                                        

                    

8' x 12' x   8' =   768 cu ft

Total Volume of Space

3008 cu ft

3. Divide the total space volume by 50 cuft to determine the Maximum Supportable Btu/Hr.

Example:

3008 cu ft ÷  50 = 60.160  x 1000 = 

6 0 , 1 6 0

Maximum Supportable Btu/Hr = 60,160 Btu/Hr

.

4. Add the rated (Btu/hr) of all fuel burning appliances in the "space" to determine Actual Btu/Hr Used.

Example:

Vent free gas log heater

40,000 Btu/Hr

Gas water heater                   

                    

32,000 Btu/Hr

Actual Btu/Hr Used

7 2 , 0 0 0   B t u / H r

Note: Do not include direct vent gas appliances.

5. Compare Maximum Supportable Btu/Hr against Actual Btu/hr Used.
•If Actual Btu/Hr Used is greater than Maximum Supportable Btu/Hr then space is CONFINED.
•If the Actual Btu/Hr Used is less than Maximum Supportable Btu/Hr then space is UNCONFINED.

60,160 Btu/Hr = Maximum Supportable Btu/Hr

             

- 72,000 Btu/Hr = Actual Btu/Hr Used

             

- 11,840 Btu/Hr = Excess Non-Supportable Btu/Hr

In the example, because the Actual Btu/Hr Used exceeds the Maximum Supportable Btu/hr the space would
be considered a Confined Space requiring you to either increase the Maximum Supportable Btu/Hr,
decrease
 the Actual Btu/Hr Used or operate as a Vented Appliance (see page 3).

Adequate Combustion And Ventilation Air Options:

Increase the Maximum Supportable Btu/Hr by adding to the number of rooms which comprise the "Space".
To do this you must ether completely remove the door to an adjoining room or provide two permanent ventilation
grills; one within 12" of the ceiling and another within 12" of the floor.

Increase the Maximum Supportable Btu/Hr by providing extra fresh air using ventilation grills and ducts to the
outdoors. You must provide two permanent openings, one within 12" of the ceiling and another within 12" of the
floor. Connect these directly to the outdoors or spaces open to the outdoors, e.g., attics or crawl spaces.

Follow the 

National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation

 for

required size of ventilation grills or ducts.

Lower the Actual Btu/Hr Used by relocating other gas burning appliances outside the "space" or installing a
lower Btu/Hr heater. In the example, the maximum Btu/Hr of the heater could be no more than 28,160 Btu/Hr.

For our example, we have chosen to add to our Total Volume of the Space by removing the door to an adjoining
study and increasing our Maximum Supportable Btu/Hr by the volume of the additional room. The new "space"
calculations, including the additional adjoining room are:

Living room/dining room & Kitchen

3008 cu ft

Study (9' x 10' x  8')                                 

                    

  720 cu ft

Total volume of space

3728 cu ft

The new

 Maximum Supportable Btu/Hr

  = (3728 cu ft  ÷ 50 cu ft ) x 1000 = 

7 4 , 5 6 0   B t u / H r

74,560 Btu/Hr = Maximum Supportable Btu/Hr

             

- 72,000 Btu/Hr = Actual Btu/Hr Used

  2,560 Btu/Hr = Remaining Supportable Btu/Hr

Because the Actual Btu/Hr used is now less than the Maximum Supportable Btu/Hr, the space is

considered an Unconfined Space. No additional fresh combustion and ventilation air would be required.

4

Summary of Contents for DFC18-DFC1-R-N

Page 1: ...isted ventless firebox enclosure DO NOT install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Improper installation adjustment alteration ...

Page 2: ...e a CHILLBUSTER is installed 3 The minimum size in inches of the fireplace in which this CHILLBUSTER is to be installed must be as follows SET SIZE MODEL NUMBER FRONT WIDTH HEIGHT DEPTH 18 24 30 18 24 30 18 24 30 18 24 30 K W KW 18 C1C M S R N P 23 000 BTU HR K W KW 24 C1C M S R N P 23 000 BTU HR K W KW 30 C1D M S R N P 23 000 BTU HR K W KW 18 C1A M S R N P 40 000 BTU HR K W KW 24 C1A M S R N P 40...

Page 3: ...BUSTER is very realistic in appearance it is not a real wood burning fireplace Matches paper garbage or any other material must not be thrown on top of the logs or into the flames Avoid contact with the logs grate or any other part which may be hot Always ensure that the fireplace screen is closed when the appliance is operating State or local codes may only allow operation of this appliance in a ...

Page 4: ...rtable Btu Hr 72 000 Btu Hr Actual Btu Hr Used 11 840 Btu Hr Excess Non Supportable Btu Hr In the example because the Actual Btu Hr Used exceeds the Maximum Supportable Btu hr the space would be considered a Confined Space requiring you to either increase the Maximum Supportable Btu Hr decrease the Actual Btu Hr Used or operate as a Vented Appliance see page 3 Adequate Combustion And Ventilation A...

Page 5: ...mbing electrical and gas lines and at other openings WARNING CARBON MONOXIDE POISONING MAY LEAD TO DEATH When used without fresh air gas log sets may give off carbon monoxide an odorless colorless poisonous gas Some people pregnant women persons with heart or lung disease anemia or under the influence of alcohol and persons at high altitudes are more affected by carbon monoxide than others Early s...

Page 6: ...BOX Figure 3 4 Standard Fireplace Hood with a minimum 4 inch horizontal projection beyond vertical surface ABOVE hood as provided by most major fireplace manufacturers IF YOU CANNOT MEET THESE MINIMUM CLEARANCES YOU MUST OPERATE HEATER WITH CHIMNEY FLUE DAMPER OPEN Operate as a VENTED Heater See Page Three ALL APPLICATIONS VENTED and VENT FREE OPERATION ASSEMBLY AND INSTALLATION INSTALLING CHILLBU...

Page 7: ...P VIEW FRONT VIEW Front Log Rear Log Top Log Large R Top Log Large L Top Log Small L Top Log Small R Front Log Rear Log Top Log Large R Top Log Small R Top Log Large L Top Log Small L Main burner 24 30 sets 24 30 sets Figure 5 Figure 6 WARNING Failure to position parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damag...

Page 8: ... Valve Knob until air is bled and gas flows to pilot Press PIEZO IGNITOR Button Figure 9 to light pilot Continue to hold valve knob in until Pilot remains lit when knob is released 5 Slowly turn knob to ON The rear burner will light from the pilot The front burner will light from the carry over tube 6 If appliance fails to light or if pilot goes out repeat steps 1 through 5 7 For complete shutdown...

Page 9: ...rared and operate instantly and requires you to aim and hold the transmitter for 1 to 3 seconds to operate Manual Operation Receiver switch position ON or OFF does not require batteries Remote Operation Requires good batteries If you turn the gas log on using the remote control and then turn the set off by sliding the receiver switch from REMOTE to OFF when you replace the switch to REMOTE it will...

Page 10: ... the area around the CHILLBUSTER free and clear from debris From time to time visually check pilot and burner flames for proper appearance Figures 15 and 16 Normal flame color should be yellow body surrounded by a hard blue haze The pilot air shutters and burners must be free of lint and dirt for optimum performance Air shutters which have been closed or are obstructed with debris will not allow s...

Page 11: ... 20 21 22 24 26 31 30 23 25 2 8 32 33 40 41 42 43 50 51 60 61 62 1 O22 Burner 40 000 BTU or 9 Push Button Ignitor DFC1 C1C Double Face 43 Valve Knob O38 Burner 23 000 BTU 10 Inlet Aluminum Connector 30 Grate 2 Pilot Manifold Tubing C1A C and C1B D 31 Front Logs 2 MILLIVOLT SWITCH SETS 3 O D S Assembly Natural or 20 Grate 32 Top Logs 2 Large 50 Manual 3 Way Switch and O D S Assembly Propane 21 Fron...

Page 12: ...y as set forth herein and applies only for the periods designated above 2 RASMUSSEN shall not be liable for any loss damage incidental or consequential damages of any kind whether based upon warranty contract or negligence arising in connection with the sale use or repair of the product Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitat...

Page 13: ...CPW CB 2 96 CHANGES next page 1 standard update z21 11 2a 2001 DUE 4 03 standard update z21 11 2b 2002 DUE 12 03 13 ...

Reviews: