IMPORTANT INFORMATION
1.
This gas log set must be installed only in a solid-fuel burning fireplace with a working flue and constructed of non
combustible material. The flue must exhaust all products of combustion.
2.
The minimum permanent free opening of the fireplace chimney or chimney damper must be at least (
*
Square
Inches - see ITEM 5 below) based on a minimum chimney height of at least 10 feet. The area of the flue must not
be less than 1/10 the area of the fireplace opening.
3.
Solid fuels shall not be burned in a fireplace where a decorative appliance is installed.
4.
The chimney damper must be fixed in a manner to maintain permanent free opening as outlined in item 2 above at
all times. To accomplish this, install the damper clamp (provided) on the edge of the damper blade to prevent its
closing or drill a hole or holes in the damper.
5.
The minimum size (in inches) of the fireplace in which the log set is to be installed must be as follows:
LOG
S I Z E
BURNER
S I Z E
HEIGHT
D E P T H
WIDTH
*
MINIMUM
CHIMNEY
OPENING
18 or 21
24 or 27
30 or 36
18 INCH
24 INCH
30 INCH
18
18
18
14
14
14
30
36
42
39 SQ IN
51 SQ IN
64 SQ IN
6.
A fire place screen must be in place when the log set is in operation and, unless other provisions for combustion
air are provided, the screen shall have opening(s) for introduction of combustion air. Glass doors are not certified
with the Log Set. However, if used, Glass Doors must be wide open when the burner is on to allow air for safe
combustion and venting.
7.
The minimum inlet gas supply pressure for the purpose of input adjustment shall be 6 inches of water column on
natural gas and 11 inches of water column on LP gases.
8.
The maximum inlet gas supply pressure shall be 7 inches of water column on natural gas and 14 inches of water
column on LP gases.
9.
The installation and the provision for combustion and ventilation air must conform with the National Fuel Gas Code
ANSI Z223.1 - Latest Edition.
10. The gas log set and its individual shutoff valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The gas log set must be
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
11. The area around the gas log set must be clear and free from combustible materials, gasoline and any other
flammable vapors and liquids.
12. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the control system and any gas control which has been under
water.
WARNING: CARBON MONOXIDE POISONING MAY LEAD TO DEATH
When used without fresh air, gas log set may give off carbon monoxide, an odorless,
colorless, poisonous gas.
Some people, pregnant women, persons with heart or lung disease, anemia, or under the
influence of alcohol and persons at high altitudes are more affected by carbon monoxide
than others.
Early signs of carbon monoxide poisoning resemble the flu: Headache, dizziness, and/or
nausea. If you have these signs, the gas log may not be installed or working properly, or
the chimney flue may be blocked. GET FRESH AIR AT ONCE! Have gas log set and
chimney flue serviced before using again.
DAMPER MUST BE WIDE OPEN WHILE BURNING
OPEN A WINDOW AN INCH OR TWO FOR
FRESH AIR WHEN USING YOUR GAS LOG