IMPORTANT INFORMATION

1.

This gas log set must be installed only in a  solid-fuel burning fireplace with a working flue and constructed of non 
combustible material.  The flue must exhaust all products of combustion.

2.

The minimum permanent free opening of the fireplace chimney or chimney damper must be at least (

*

Square 

Inches - see ITEM 5 below) based on a minimum chimney height of at least 10 feet.  The area of the flue must not 
be less than 1/10 the area of the fireplace opening. 

3.

Solid fuels shall not be burned in a fireplace where a decorative appliance is installed.

4.

The chimney damper must be fixed in a manner to maintain permanent free opening as outlined in item 2 above at 
all times.  To accomplish this, install the damper clamp (provided) on the edge of the damper blade to prevent its 
closing or drill a hole or holes in the damper.

5.

The minimum size (in inches) of the fireplace in which the log set is to be installed must be as follows:

LOG

S I Z E

BURNER

S I Z E

HEIGHT

D E P T H

WIDTH

 * 

MINIMUM
CHIMNEY
OPENING

18 or 21
24 or 27
30 or 36

18 INCH
24 INCH
30 INCH

18
18
18

14
14
14

30
36
42

39 SQ IN
51 SQ IN
64 SQ IN

6.

A fire place screen must be in place when the log set is in operation and, unless other provisions for  combustion
air are provided, the screen shall have opening(s) for introduction of combustion air.  Glass  doors are not certified 
with the Log Set.  However, if used, Glass Doors must be wide open when the  burner is on to allow air for safe 
combustion and venting.

7.

The minimum inlet gas supply pressure for the purpose of input adjustment shall be 6 inches of water column on 
natural gas and 11 inches of water column on LP gases.

8.

The maximum inlet gas supply pressure shall be 7 inches of water column on natural gas and 14 inches of water 
column on LP gases.

9.

The installation and the provision for combustion and ventilation air must conform with the National Fuel Gas Code 
ANSI Z223.1 - Latest Edition.

10.  The gas log set and its individual shutoff valve must  be  disconnected  from  the gas supply piping system during 

any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).  The gas log  set must be 
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure 
testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

11.  The area around the gas log set must be clear and free from combustible materials, gasoline and any other 

flammable vapors and liquids.

12.  Do not use this appliance if any part has been under water.  Immediately call a qualified service technician to 

inspect the appliance and to replace any part of the control system and any gas control which has been under 
water.

WARNING: CARBON MONOXIDE POISONING MAY LEAD TO DEATH

When used without fresh air, gas log set may give off carbon monoxide, an odorless,
colorless, poisonous gas.
Some people, pregnant women, persons with heart or lung disease, anemia, or under the
influence of alcohol and persons at high altitudes are more affected by carbon monoxide
than others.
Early signs of carbon monoxide poisoning resemble the flu: Headache, dizziness, and/or
nausea.  If you have these signs, the gas log may not be installed or working properly, or
the chimney flue may be blocked.  GET FRESH AIR AT ONCE!  Have gas log set and
chimney flue serviced before using again.  

DAMPER MUST BE WIDE OPEN WHILE BURNING

OPEN A WINDOW AN INCH OR TWO FOR

FRESH AIR WHEN USING YOUR GAS LOG

Summary of Contents for TR 3000 SERIES

Page 1: ...M N P 30 SwitchPilotControl PA PR MA NA XF WSA LS UA 36 TR30 S N P WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life Read these Instructions carefully and retain them for future use THESE APPLIANCES ARE CERTIFIED TO THE FOLLOWING STANDARDS TR 18 TR 24 TR 30 M Manual or S Switch Vented Decorative Appliance ...

Page 2: ... column on LP gases 8 The maximum inlet gas supply pressure shall be 7 inches of water column on natural gas and 14 inches of water column on LP gases 9 The installation and the provision for combustion and ventilation air must conform with the National Fuel Gas Code ANSI Z223 1 Latest Edition 10 The gas log set and its individual shutoff valve must be disconnected from the gas supply piping syste...

Page 3: ...lue MUST BE FREE OF ANY OBSTRUCTIONS 2 Turn off gas supply to fireplace 3 Clean fireplace floor of any ashes 4 Attach damper clamp over edge of fireplace damper blade as shown When installed properly damper clamp prevents accidental full closure of damper See FIGURE 1 If unable to install provided damper clamp consult IMPORTANT INFORMATION on front page of these directions Damper Stop Clamp Damper...

Page 4: ...ion 1 Place lighted match on right side of FRONT BURNER TRAY near inlet end of burner FIGURE 3 DO NOT HOLD MATCH IN HAND 2 Slowly open PRIMARY GAS SUPPLY VALVE and wait for burner to light FIGURE 3 3 Adjust PRIMARY GAS SUPPLY VALVE to obtain desired flame height Ensure adequate gas supply is available to operate FRONT BURNER TRAY and MIDDLE BURNER TRAY TR 18 24 30 M MANUAL PILOT CONTROL PILOT LIGH...

Page 5: ...knob until air is bled and gas flows to pilot Press PIEZZO IGNITOR BUTTON FIGURE 8 to light pilot Continue to depress MILLIVOLT GAS VALVE Knob until pilot remains lit when knob is released approximately 60 to 90 seconds 6 If Pilot does not remain lit repeat steps 1 through 5 and allow more time after Pilot Lighting before releasing knob PILOT FLAME ADJUSTMENT TR 18 24 30 S SWITCH PILOT CONTROL PIL...

Page 6: ...RC wireless remotes may be located REAR BURNER ADJUSTMENT TOP BURNER CONTROL VALVE OFF ON FIGURE 11 REAR BURNER CONTROL VALVE REAR BURNER CONTROL VALVE Once the burners have been lit the REAR BURNER can be adjusted independently of the MIDDLE and BOTTOM BURNERS by adjusting the REAR BURNER CONTROL VALVE FIGURES 3 11 To achieve the desired flame effect turn the REAR BURNER CONTROL VALVE countercloc...

Page 7: ...LER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 PARTS LIST 1 Pine Cone 10 Gas Distribution Assembly 17 Grate 23 Primary Connector Tubing 2 Top Log Small Left 11 Rear Cover Plate 18 Middle Burner Manifold 24 Control Mounting Plate 3 Top Log Large left 12 Top Burner Control Valve Tubing 25 Gas Regulator Assembly 4 Top Log Small Right Manifold Tubing 19 Middle ...

Page 8: ... RASMUSSEN shall not be liable for any loss damage incidental or consequential damages of any kind whether based upon warranty contract or negligence arising in connection with the sale use or repair of the product Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you 3 The maximum liability of RASMUSSE...

Reviews: