background image

Page 5

Step 6: Wiring the Emergency Phones to the SmartRescue

Use twisted, shielded, 22 or 24 AWG, 2 pair cable between the phones and the SmartRescue. The maximum 

communication run is 5,100’.

Connecting Wire Run:

To SmartRescue: 

Insert 4 wires for each phone as shown in 

Diagram B

.

To Phone: 

Wire out to a standard 2 pair RJ11 connector. Pins 2 and 3 (red and green) carry the outside phone line. 

Pins 1 and 4 (yellow and black) are the intercom pair.

Diagram B

SmartRescue

NEUTRAL

120vac

HOT

Handset Connection 

Dedicated Analog 

Phone Line 

24v Power Input 

Battery Backup 

Optional Sub-Master 

Phone Ports 

RJ11 

Plug-In

Transformer 

Phone Push Connector 1

Phone Push Connector 2

Phone Push Connector 3

Phone Push Connector 4

Phone Push Connector 5

Phone Push Connector 6

Phone Push Connector 7

Phone Push Connector 8

Phone Push Connector 9

Phone Push Connector 10  

Supplied by

RATH®

Supplied by

RATH®

GROUND

Yellow (PIN-1)
Green (PIN-2)
Red (PIN-3)
Black (PIN-4)   

 

L N       -V +V

Wiring Emergency Phones to SmartRescue

Note: 

When using the SmartRescue for Area of Refuge applications, it is recommended to use a biscuit jack for 

connecting each phone. This will prevent loose connections that can cause the system to malfunction. Biscuit 

jacks are available from RATH® by request.

Note:

 DO NOT use aluminum conductors with push-in terminals.

Note:

 Shields from the cabling runs (if used) should be attached to 

one of the mounting screws on the SmartRescue housing.

Note:

 Line impedance of the phone line is 600 ohms.

Step 7:

Mount the front cover back on to the enclosure.

Emergency Phone

Yellow (PIN-1)
Green (PIN-2)
Red (PIN-3)
Black (PIN-4)

Page 4

Diagram B

0

2

5

3

1

7 8  9 

*

#

0

2

5

3

1

7 8  9 

*

#

0

2

5

3

1

7 8  9 

*

#

0

2

5

3

1

7 8  9 

*

#

0

2

5

3

1

7 8  9 

*

#

2 Pair- Twisted 

24-22ga 

2 Pair- Twisted 

24-22ga 

2 Pair- Twisted 

24-22ga 

2 Pair- Twisted 

24-22ga 

2 Pair- Twisted 

24-22ga 

1 Pair Wire 
From Telco 

Plug-In 

Transformer 

GROUND 

120vac HOT 

NEUTRAL 

GROUND 

120vac HOT 

NEUTRAL 

GROUND 

120vac HOT 

NEUTRAL 

GROUND 

120vac HOT 

NEUTRAL 

GROUND 

120vac HOT 

NEUTRAL 

SUB-MASTER 1

SUB-MASTER  2

OPERATION:

1.

  SOLID LIT 

LED

 (PHONE, SUB-MASTER

     OR RESCUE SERVICES) INDICATES

     CALL IN PROGRESS. 

2.

  SLOW BLINKING 

LED

 INDICATES

     CALL ON HOLD.

3.

  LIFT HANDSET.

4.

  PRESS YELLOW 

TALK/HOLD

 BUTTON TO CALL 

     IN TO A SPECIFIC SUB-MASTER. IF THE GREEN 

     LED

 IS LIT YOU WILL JOIN CONVERSATION.  

5.

  PRESS BLACK 

TALK/HOLD

 BUTTON TO CALL IN 

     TO A SPECIFIC PHONE. IF THE GREEN 

LED 

IS 

     LIT YOU WILL JOIN CONVERSATION.

6.

  PRESS 

TALK/HOLD

 BUTTON AGAIN TO PLACE

     CONVERSATION ON HOLD.

7.

  PRESS RED 

DISCONNECT CALL TO RESCUE 

     SERVICES 

BUTTON TO END EXTERNAL CALL.

     ANY PHONE AND SUB-MASTER ORIGINALLY 

     TALKING REMAIN IN CONVERSATION WITH

     THIS UNIT.

8.

  HANG UP HANDSET TO END CALLS TO PHONE 

     AND SUB-MASTER.

BATTERY

 POWER

PHONE 1

PHONE 2

PHONE 3

PHONE 4

PHONE 5 

DISCONNECT 

CALL TO 

RESCUE 

SERVICES

SMARTRESCUE PHONE - 5

READ ALL OPERATING STEPS

BEFORE PROCEEDING

RESCUE SERVICES

SOLID LIGHT: CALLING

BLINKING LIGHT: RECEIVED

EMERGENCY PHONE

SOLID LIGHT: CALLING

BLINKING LIGHT: RECEIVED

EMERGENCY PHONE

SOLID LIGHT: CALLING

BLINKING LIGHT: RECEIVED

EMERGENCY PHONE

SOLID LIGHT: CALLING

BLINKING LIGHT: RECEIVED

EMERGENCY PHONE

SOLID LIGHT: CALLING

BLINKING LIGHT: RECEIVED

EMERGENCY PHONE

24/5VA

24/5VA

24/5VA

24/5VA

24/5VA

Wiring Diagram with Individual Transformers

N56W24720 N. Corporate Circle  •  Sussex, WI 53089

 800-451-1460  •  www.rathcommunications.com

12/21

Twisted, Shielded 

Wire Recommended

Summary of Contents for 2500-205B

Page 1: ...SmartRescue 5 10 Installation Operations Manual N56W24720 N Corporate Circle Sussex WI 53089 800 451 1460 www rathcommunications com RP8500510 Ver 4 11 19 WARRANTY 2YEAR...

Page 2: ...ations com Table of Contents SmartRescue 5 10 Installation Powering the SmartRescue Wiring Emergency Phones to SmartRescue Typical Wiring Diagrams for Elevators Typical Wiring Diagram for Areas of Ref...

Page 3: ...s Pre Installation Requirements Step 1 Remove the front cover from the SmartRescue and mount the SmartRescue back box to the wall using suitable mounting screws not included Step 2 Punch out the condu...

Page 4: ...d 120vac outlet Option 2 Hard Wired Transformer Connect the hot wire of the 120vac to the L screw Connect the neutral wire of the 120vac to the N screw Connect the ground wire of the 120vac to the gro...

Page 5: ...phone line is 600 ohms Step 7 Mount the front cover back on to the enclosure Emergency Phone Yellow PIN 1 Green PIN 2 Red PIN 3 Black PIN 4 Diagram B 0 2 5 3 1 4 6 7 8 9 0 2 5 3 1 4 6 7 8 9 0 2 5 3 1...

Page 6: ...SPECIFIC PHONE IF THE GREEN LED IS LIT YOU WILL JOIN CONVERSATION 6 PRESS TALK HOLD BUTTON AGAIN TO PLACE CONVERSATION ON HOLD 7 PRESS RED DISCONNECT CALL TO RESCUE SERVICES BUTTON TO END EXTERNAL CAL...

Page 7: ...HOLD 7 PRESS RED DISCONNECT CALL TO RESCUE SERVICES BUTTON TO END EXTERNAL CALL ANY PHONE AND SUB MASTER ORIGINALLY TALKING REMAIN IN CONVERSATION WITH THIS UNIT 8 HANG UP HANDSET TO END CALLS TO PHON...

Page 8: ...VED EMERGENCY PHONE SOLID LIGHT C ALLING BLINKING LIGHT RECEIVED EMERGENCY PHONE SOLID LIGHT C ALLING BLINKING LIGHT RECEIVED EMERGENCY PHONE Typical Wiring Diagram for Area of Refuge Applications 1 P...

Page 9: ...rgency Number as entered in b Stop 4 To exit program mode press and hold Stop for 2 3 seconds until warble sound Program the Location Message Note This is always done unless your Call Center requests...

Page 10: ...hone that placed the call c If call is not answered at the SmartRescue the Emergency Phone will hang up and dial the second number programmed into the phone d The Rescue Services LED located next to t...

Page 11: ...6 9 TB1 Relay SmartRescue System Activation Relay When an Emergency Phone has been activated this relay changes from NO to closed It can be connected to a strobe or other notification means Connectio...

Page 12: ...SmartPhone is correct Two way communication from SmartPhone is poor There could be feedback on the line Adjust the VR1 and VR2 Verify wiring is not spliced onto the phone line cord SmartRescue will n...

Page 13: ...or indoor use only Operating temperature 32 F to 120 F 0 C to 49 C TB1 Relay Load Current 130mA Load Voltage 350vdc or vac Note Input power circuit battery circuit and phone circuits are supervised in...

Page 14: ...61 294 96 1 03 26 25 1 27 32 38 0 32 8 05 0 88 22 23 4 34 110 17 0 45 11 41 0 50 12 70 1 0 56 319 09 11 61 294 96 0 33 8 49 5 81 147 48 0 28 7 18 FRONT PANEL COVER LEFT SIDE BOTTOM SIDE CONTROL INSIDE...

Page 15: ...ED Y G R B Y G R B Y G R B Y G R B Y G R B Y G R B Y G R B Y G R B Y G R B Y G R B 1 2 3 4 5 6 7 8 9 10 HOOK SWITCH Y G R B Y G R B 0 69 17 50 0 84 21 27 0 69 17 46 0 69 17 46 0 25 6 35 0 13 3 18 4 02...

Reviews: