5. HYDRAULIC INSTALLATION
5.6 REQUIREMENTS FOR THE QUALITY OF THE HEATING WATER
Parameter
Unit
Concentration
Copper brazed
pH level
/
< 6.0
6.0 - 7.5
7.5 - 8.5
8.5 - 10.0
> 10
-
°
+
°
°
Conductivity
µS/cm
< 10
10 - 500
500 - 1,000
> 1,000
+
+
°
-
Chloride
mg/L
< 10
10 - 50
50 - 80
80 - 100
100 - 1,000
> 1,000
+
+
+
+
°
-
Free chlorine
mg/L
< 0.5
0.5 - 1.0
1.0 - 5.0
> 5.0
+
+
°
-
Total hardness
°dH
< 5
5 - 15
15 - 30
> 30
+
+
°
-
Ammonia (NH
3
, NH
4
+
)
mg/L
< 2
2 - 20
> 20
+
°
-
Alkalinity (HCO
3
)
mg/L
< 60
60 - 300
> 300
+
+
°
Sulphate (SO
4
2-
)
mg/L
< 100
100 - 300
> 300
+
°/-
-
HCO
3
/ SO
4
2-
mg/L
> 1.5
< 1.5
+
°/-
Nitrates (NO
3
)
mg/L
< 100
> 100
+
°
Hydrogen sulphide (H
2
S)
mg/L
< 0.05
> 0.05
+
°/-
Free carbon dioxide (CO
2
)
mg/L
< 5
5 - 20
> 20
+
°
-
Manganese
mg/L
< 0.1
> 0.1
+
°
Iron (Fe)
mg/L
< 0.2
> 0.2
+
°
Aluminium
mg/L
< 0.2
> 0.2
+
°
It must be ensured that the heating water meets all the requirements. If two or more criterias are not optimal (°) or if
one criteria does not meet the requirements (-), no claim under guarantee will be considered.
A maximum of
50 % glycol
may be present in the system water.
Summary of Contents for WP Grid-HiQ CF06
Page 1: ...Technical Document state 11 05 2020 WP Grid HiQ CF06...
Page 50: ...50 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 52: ...52 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 54: ...54 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 56: ...56 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 62: ...62 13 ANNEX 13 3 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE...
Page 64: ...64 13 ANNEX 13 3 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE...
Page 66: ...66 13 ANNEX 13 4TECHNICAL DATA RSM610...
Page 78: ...78 13 9 LABEL 13 ANNEX...