11. WARTUNG & INSTANDHALTUNG
copper-brazed stainless steel plate heat exchanger
durability recommendation copper solder:
electrical conductance (μS/cm)
10 - 500
pH value
7.5 - 9.0
carbon dioxide (H2CO
3
)
< 5
total hardness (°dH)
4.0 - 8.5
primary liquid content (litre)
1.554
secondary liquid content (litre)
1.665
admissible operting pressure (bar)
25
admissible operating temperature (°C)
155
11.4 PLATE HEAT EXCHANGER: CLEANING/WATER VALUES
ATTENTION!
All acids and bases are dangerous substances and should be used with great care.
Warranty
ratiotherm offers a 12-month warranty from the date of installation, but in no case longer than 15 months
after the date of delivery.
The warranty only covers manufacturing and material defects.
Liability committee
The performance of ratiotherm‘s brazed compact heat exchangers is only achieved if the installation,
maintenance and operating conditions correspond to the specifications in the manual.
ratiotherm is not liable for brazed compact heat exchangers for which the criteria listed in the following
table are not met.
After cleaning, do not forget to rinse the heat exchanger thoroughly with clean water.
A solution of 1 to 2 % sodium hydroxide (NaOH) or sodium hydrogen carbonate (NaHCO3) before the final
rinse ensures that all acids are neutralized.
Perform cleaning at regular intervals.
Summary of Contents for WP Grid-HiQ CF06
Page 1: ...Technical Document state 11 05 2020 WP Grid HiQ CF06...
Page 50: ...50 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 52: ...52 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 54: ...54 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 56: ...56 13 ANNEX 13 1 ELECTRICAL PLAN...
Page 62: ...62 13 ANNEX 13 3 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE...
Page 64: ...64 13 ANNEX 13 3 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE...
Page 66: ...66 13 ANNEX 13 4TECHNICAL DATA RSM610...
Page 78: ...78 13 9 LABEL 13 ANNEX...