Use and maintenance manual Mia 90
Pag.39
Rev.2 03/03/2021
Chronothermostat
📌
The PROGRAMMABLE THERMOSTAT function is only active in HEATING mode.
With the Chrono-thermostat function you can program the automatic switch ON/OFF of the stove for each day of the week for each
day of the week in 4 independent time intervals (SET CHRONO 1-2-3-4). Below are given the steps for accessing the relative menu
starting from “Home” mode.
To exit the page and return to “Home” page, press the button repeatedly.
The exit key shows the CHRONO menu to set other variables related to the menu functions.
Set air - pellet
The setting of the PELLET-FLOW mixture allows to adjust the combustion by varying the quantity of pellets loaded in the brazier
and/or the quantity of air. In fact, by its nature, pellets vary in grain size and composition: even bags of pellets of the same brand
can have different characteristics.
If combustion is not optimal, vary the flow parameter to adjust the combustion air. If air regulation alone is not sufficient, it may also
be necessary to modify the pellet parameter.
⚠
Combustion regulation is an operation that requires a lot of experience. We recommend that you contact an Authorised
Service Centre to calibrate the stove appropriately.
Manuale utente PALMARE IDRO TOUCH RADIO
Manuale utente PALMARE IDRO TOUCH RADIO
Pag.32
Pag.33
Vers. 01 del 07/04/15
Vers. 01 del 07/04/15
Press the key
“confirm” to
access the
SETUP
SETTINGS
Press the key
“selection” to switch
to the function
VERSION FW.
Press the key
“confirm”
to access the function
To access the next setting, follow the steps given above or simply remove and replace the batteries.
The device resets and prompts you again to select the language you want to set.
Settings > Language
Settings > Adjust
Use the UP/DOWN keys to change the value read by the
room temperature probe installed inside the handheld
set, with respect to a reference value.
The value can vary from -10°C to 10°C.
The standard value is 0°C.
By pressing the following key you will confirm of data
and switch to the page within SETTINGS menu
The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and
the room temperature fan installed inside them.
Below are the messages shown on display when the stove is equipped with ventilation system.
To exit the page and return to Stand-by page, press the button repeatedly.
VENTILATION menu (function only for models in which the same is specified in the dedicate user’s manual)
Control: v
entilation can be set from 0 to AUTO where 0 indicates that the same is disabled, setting from MIN to MAX enables selecting
the heat distribution speed. If set to AUTO, the ventilation follows the power set on the stove.
Press the increase/decrease keys
“increase/decrease”
to change the ventilation.
To exit the page and return to Stand-by page, press the button repeatedly.
The exit key shows the CHRONO menu to set other variables related to the menu functions.
Press the key
“enter” at the end of the
setting, from the following
CHRONO page
The temperature read by the handheld unit controls the modulation of the stove. If you want to adjust the ventilation by
adjusting the stove, set the fan to A mode as shown in the relative chapter.
Press the key
“access menu” to
access the
MENU page
Press the key
“confirm”
to access the
USER page
Press the key
“confirm”
to quickly switch to
VENTILATION.
Press the increase/decrease keys
“increase/decrease”
to change the ventilation.
Pages displayed upon the activation of advanced layouts
By activating a layout different from the standard (layout 0), even if maintaining the same functions of the menu, the “Stand-by” page will
display all connected utilities such as the temperature of the boiler of the puffer.
Below is shown the new display mode and the function of every icon for every layout, to change the various settings.
Layout 1 (DHW heating control)
The following layout can be used when you have a boiler that is not equipped with plate heat exchanger and you intend to buy a puffer
that should be connected to the circuit to produce hot domestic water.
In this type of circuit, room temperature is controlled however by the handheld unit which, being a radio device, acts as a remote
chronothermostat. The boiler is managed by the thermostove through a contact or immersion probe (not supplied) connected directly
to the back of the stove. Below is shown the new “Stand-by” mode.
By setting the SUMMER function, the 3-way valve remains fixed in a single position, enabling the release of heat output
by the stove exclusively inside the boiler. As soon as this condition is reached, the boiler switches to ECO STOP mode.
The operation is the same as for the basic layout except for the fact that in this layout, the boiler exchanges heat directly in the
boiler (priority); when the temperature set is reached, the 3-way valve changes its position and the boiler starts exchanging heat within
the heating circuit. From this moment, the stove is controlled by the radio handheld unit for contolling the room
temperature or via H2 setting (see the operation with layout 0 to find the data on modulation, eco stop etc.).
The 3-way valve is directed again into the boiler when:
- there is a request from the Boiler;
- there is a requested from the flow switch (optional, if connected).
The stove restarts from Eco-stop or Stand by mode according to heating requests or boiler requests.
T°C Boiler
From STAND BY mode, press
the ARROW key UP
to set the
room T°C
and DHW boiler T°C that you
desire.
Boiler water T°C
From STAND BY mode, press
the ARROW key DOWN
to set
the boiler water T°C
that you desire.
Press the key
“V” from STAND BY page
to display the actuale states and
the room temperature
Chrono function
By enabling the chrono function, it is possible to control the ventilation speed for each program as shown in the logic above.
Press the key
“access menu” to
access the
MENU page
Press the key
“confirm”
to access the
USER page
Press the key
several times
to quickly switch to
CRONO-THERMOSTAT.
If the type of system designed requires controlling the 3-way valve (diagram 1 and 3), it is necessary to purchase the
optional kit from the retailer or the authorized Ravelli dealer.
DATE-TIME
DATE-TIME
ENABLE EXT. T
ENABLE EXT. T
SEASON
SEASON
CONTRAST
CONTRAST
FW VERSION
FW VERSION
LANGUAGE
LANGUAGE
ADJUST
ADJUST
ADJUST
MENU
USER
TECHNICIAN
VENTILATION POW.
USER
POWER SETTING
CHRONOTHERMOSTAT
SCREW LOADING
SET AIR-PELLET
MENU
USER
TECHNICIAN
USER
USER
POWER SETTING
POWER SETTING
SET AIR-PELLET
SET AIR-PELLET
CHRONOTHERMOSTAT
CHRONOTHERMOSTAT
SCREW LOADING
SCREW LOADING
CHRONO
CHRONO
ENABLE CHRONO
ENABLE CHRONO
ENABLE CHRONO
ENABLE CHRONO
VENTILATION POW.
SET CHRONO 1
SET CHRONO 1
SET CHRONO 2
SET CHRONO 2
SET CHRONO 3
SET CHRONO 3
SET CHRONO 4
SET CHRONO 4
POWER MOD
PUMP
3-WAY VALVE HEAT
PRESSURE 1.1 BAR
HH T .
21°C
MANUFACTURER’S
MANUFACTURER’S
Manuale utente PALMARE IDRO TOUCH RADIO
Manuale utente PALMARE IDRO TOUCH RADIO
Pag.32
Pag.33
Vers. 01 del 07/04/15
Vers. 01 del 07/04/15
Press the key
“confirm” to
access the
SETUP
SETTINGS
Press the key
“selection” to switch
to the function
VERSION FW.
Press the key
“confirm”
to access the function
To access the next setting, follow the steps given above or simply remove and replace the batteries.
The device resets and prompts you again to select the language you want to set.
Settings > Language
Settings > Adjust
Use the UP/DOWN keys to change the value read by the
room temperature probe installed inside the handheld
set, with respect to a reference value.
The value can vary from -10°C to 10°C.
The standard value is 0°C.
By pressing the following key you will confirm of data
and switch to the page within SETTINGS menu
The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and
the room temperature fan installed inside them.
Below are the messages shown on display when the stove is equipped with ventilation system.
To exit the page and return to Stand-by page, press the button repeatedly.
VENTILATION menu (function only for models in which the same is specified in the dedicate user’s manual)
Control: v
entilation can be set from 0 to AUTO where 0 indicates that the same is disabled, setting from MIN to MAX enables selecting
the heat distribution speed. If set to AUTO, the ventilation follows the power set on the stove.
Press the increase/decrease keys
“increase/decrease”
to change the ventilation.
To exit the page and return to Stand-by page, press the button repeatedly.
The exit key shows the CHRONO menu to set other variables related to the menu functions.
Press the key
“enter” at the end of the
setting, from the following
CHRONO page
The temperature read by the handheld unit controls the modulation of the stove. If you want to adjust the ventilation by
adjusting the stove, set the fan to A mode as shown in the relative chapter.
Press the key
“access menu” to
access the
MENU page
Press the key
“confirm”
to access the
USER page
Press the key
“confirm”
to quickly switch to
VENTILATION.
Press the increase/decrease keys
“increase/decrease”
to change the ventilation.
Pages displayed upon the activation of advanced layouts
By activating a layout different from the standard (layout 0), even if maintaining the same functions of the menu, the “Stand-by” page will
display all connected utilities such as the temperature of the boiler of the puffer.
Below is shown the new display mode and the function of every icon for every layout, to change the various settings.
Layout 1 (DHW heating control)
The following layout can be used when you have a boiler that is not equipped with plate heat exchanger and you intend to buy a puffer
that should be connected to the circuit to produce hot domestic water.
In this type of circuit, room temperature is controlled however by the handheld unit which, being a radio device, acts as a remote
chronothermostat. The boiler is managed by the thermostove through a contact or immersion probe (not supplied) connected directly
to the back of the stove. Below is shown the new “Stand-by” mode.
By setting the SUMMER function, the 3-way valve remains fixed in a single position, enabling the release of heat output
by the stove exclusively inside the boiler. As soon as this condition is reached, the boiler switches to ECO STOP mode.
The operation is the same as for the basic layout except for the fact that in this layout, the boiler exchanges heat directly in the
boiler (priority); when the temperature set is reached, the 3-way valve changes its position and the boiler starts exchanging heat within
the heating circuit. From this moment, the stove is controlled by the radio handheld unit for contolling the room
temperature or via H2 setting (see the operation with layout 0 to find the data on modulation, eco stop etc.).
The 3-way valve is directed again into the boiler when:
- there is a request from the Boiler;
- there is a requested from the flow switch (optional, if connected).
The stove restarts from Eco-stop or Stand by mode according to heating requests or boiler requests.
T°C Boiler
From STAND BY mode, press
the ARROW key UP
to set the
room T°C
and DHW boiler T°C that you
desire.
Boiler water T°C
From STAND BY mode, press
the ARROW key DOWN
to set
the boiler water T°C
that you desire.
Press the key
“V” from STAND BY page
to display the actuale states and
the room temperature
Chrono function
By enabling the chrono function, it is possible to control the ventilation speed for each program as shown in the logic above.
Press the key
“access menu” to
access the
MENU page
Press the key
“confirm”
to access the
USER page
Press the key
several times
to quickly switch to
CRONO-THERMOSTAT.
If the type of system designed requires controlling the 3-way valve (diagram 1 and 3), it is necessary to purchase the
optional kit from the retailer or the authorized Ravelli dealer.
DATE-TIME
DATE-TIME
ENABLE EXT. T
ENABLE EXT. T
SEASON
SEASON
CONTRAST
CONTRAST
FW VERSION
FW VERSION
LANGUAGE
LANGUAGE
ADJUST
ADJUST
ADJUST
MENU
USER
TECHNICIAN
VENTILATION POW.
USER
POWER SETTING
CHRONOTHERMOSTAT
SCREW LOADING
SET AIR-PELLET
MENU
USER
TECHNICIAN
USER
USER
POWER SETTING
POWER SETTING
SET AIR-PELLET
SET AIR-PELLET
CHRONOTHERMOSTAT
CHRONOTHERMOSTAT
SCREW LOADING
SCREW LOADING
CHRONO
CHRONO
ENABLE CHRONO
ENABLE CHRONO
ENABLE CHRONO
ENABLE CHRONO
VENTILATION POW.
SET CHRONO 1
SET CHRONO 1
SET CHRONO 2
SET CHRONO 2
SET CHRONO 3
SET CHRONO 3
SET CHRONO 4
SET CHRONO 4
POWER MOD
PUMP
3-WAY VALVE HEAT
PRESSURE 1.1 BAR
HH T .
21°C
MANUFACTURER’S
MANUFACTURER’S
1
Ignition time
2
Shutdown time
3
Day of the week when the
program is active
4
Program number “chrono”
5
Power setting
6
Setting the room temperatures
1
2
3
4
5
6
MENU
USER
TECHNICIAN
PRODUCER
USER
LOADING AUGER
CHRONOTHERMOSTAT
SET AIR-PELLET
STOVE STATUS
USER
LOADING AUGER
CHRONOTHERMOSTAT
SET AIR-PELLET
STOVE STATUS
CHRONOTHERMOSTAT
ENABLE CHRONO
SET CHRONO 1
SET CHRONO 2
SET CHRONO 3
SET CHRONO 4
CHRONOTHERMOSTAT
ENABLE CHRONO
SET CHRONO 1
SET CHRONO 2
SET CHRONO 3
SET CHRONO 4
With the cooker off, the switch-on control set by the programmable thermostat remaisn active even in Cooking mode; in this case, the
heating mode is enabled automatically.
With the cooker switched on, in COOKING mode, or off, only with the grill switched on, the ON/OFF controls set by the programmable
thermostat are not taken into account.
Summary of Contents for MIA 90
Page 2: ...MANUALE D USO E MANUTENZIONE Mia 90 ...
Page 3: ......
Page 58: ...DATA INTERVENTO EFFETTUATO MANUTENZIONE ...
Page 59: ...DATA INTERVENTO EFFETTUATO MANUTENZIONE ...
Page 60: ......
Page 62: ...MANUEL D UTILISATION ET D ENTRETIEN Mia 90 ...
Page 63: ......
Page 117: ...DATE INTERVENTION ÉFFECTUÉE ENTRETIEN ...
Page 118: ...DATE INTERVENTION ÉFFECTUÉE ENTRETIEN ...
Page 119: ......
Page 120: ......
Page 122: ...USE AND MAINTENANCE MANUAL Magnus ...
Page 123: ......
Page 177: ...DATE INTERVENTION CARRIED OUT Maintenance ...
Page 178: ...DATE INTERVENTION CARRIED OUT Maintenance ...
Page 179: ......
Page 180: ......
Page 182: ...MANUAL DE USO Y MANTENIMIENTO Mia 90 ...
Page 183: ......
Page 237: ...FECHA INTERVENCIÓN REALIZADA MANTENIMIENTO ...
Page 238: ...FECHA INTERVENCIÓN REALIZADA MANTENIMIENTO ...
Page 239: ......
Page 240: ......
Page 242: ...HANDLEIDING VOOR GEBRUIK EN ONDERHOUD Mia 90 ...
Page 243: ......
Page 297: ...DATUM INTERVENTIE UITGEVOERD ONDERHOUD ...
Page 298: ...DATUM INTERVENTIE UITGEVOERD ONDERHOUD ...
Page 299: ......
Page 300: ......