The air controls of the cooker burner are factory pre-set,
however small adjustments may be necessary to suit the
site conditions. (See Fig. 21).
Turn cooker burner on.
After 15 minutes running, sample the flue gases from the
cooker burner. Lift up the RH insulating cover and
remove the countersunk headed screw (right hand side)
in the hotplate. The cooker burner should be set to 11.0-
11.5% CO
2
with a maximum smoke No. 2. Replace the
countersunk headed screw on completion ensuring that it
will not interfere with any pots and pans placed on the
hotplate.
When satisfied with combustion check, run combustion
check for boiler burner (See Page 21).
19
Commissioning Instructions
SET COMBUSTION AIR - COOKER
Fig. 21
Fig. 22
DESN 515955
DESN 515913
COOKER FLUE
SAMPLING HOLE
+
-