It should be in accordance also with any relevant requirements of the Local Authority and the relevant
recommendations of the following current British Codes of Practice:
BS.5410
Installation of oil fired space heating and hot water supply purposes. Boilers of rated output
not exceeding 44kW.
Building Regulations
J/1/2/3
Provision for introduction of air supply and discharge of products of combustion for
appliances.
BS.4543
Specification for chimney for oil fired appliances. Part 3.
Building Regulations
J/1/2/3
Provision for protection against fire and heat.
LOCATION
Appliance Hearth
This appliance must be installed on a solid level floor or base of incombustible material which is a capable of
supporting the total weight.
The location chosen for the appliance must permit installation and the provision of a satisfactory flue and an
adequate air supply. The location must also provide adequate space for servicing and air circulation around the
appliance. See
"
Installation of Appliance
"
.
Where the cooker is to stand in a recess or against a wall, in no circumstances should the tiles overlap
the cooker top plate.
OIL STORAGE -
See fig.1
The minimum recommended oil tank size is 1400 litres (300 gallons) and the Codes of Practice governing its
installation are covered by BS.5410.
The requirements for mild steel tanks should be to BS.799 Part 5. Plastic Oil Tanks to OFTEC Standard OFS
T100. The oil storage tank must be positioned with the bottom of the tank not less than 630mm, and the top not
more than 3.2m above the base of the cooker.
Oil Pipe Line
The oil line from the storage tank to the appliance must be fitted with a remote acting fire valve (such as a
Teddington KBB-66°C) located outside the building, or where the supply enters the wall on the inside of the
building and with the heat sensing phial of the fire valve, located as near as practicable on the L.H. side of the
cooker.
A 5-10 micron oil filter should also be fitted in the oil line, and the minimum size of the copper oil pipe line should
not be less than 10mm diameter.
A stop valve must be fitted near the appliance, in an accessible position.
We also recommend an additional remote acting fire valve be fitted close to the oil control valve, with its heat
sensing phial located in the burner housing, but not touching, the inner burner door.