Check for oil leaks. Ensure that the circuit board bracket and the lock out box brackets are correctly positioned.
After allowing the cooker to heat up check that the flue analysis is 11.5 CO2 of flue gases and the smoke in the
flue exit does not exceed No.2 on the baccarach smoke pump scale. Check that if the oven thermostat is
switched ‘ON’ while the boiler thermostat is switched ‘ON’ and the burner firing, that the burner stops momentarily
and re-fires, as the oven thermostat takes priority over the boiler thermostat. Check that the hotplate is sealed
around it’s edge.
TECHNICAL DATA
7. TECHNICAL DATA & SPARE PARTS LIST
Electrical Supply:- 240 ~ 50 Hz 5A Fused. Fuel:-
KEROSENE OIL MODEL: 28 seconds commercial Kerosene to BS 2869. Part 2: 1988 Class ‘C2’ GAS OIL
MODEL: 35 seconds commercial gas oil to BS 2869. Part 2: 1988 Class ‘D’/
Removable Firebricks
DESN 510244
Burner Chamber Insulation Pads
R04F3 - 20289
Boiler Side Rear Firebrick
3/20289
1-off
R04F - 321131
Boiler Side Front Firebrick
1-off
R04F3 - 20291
Boiler Back Firebrick
3/20291
1-off
R04F3 - 20292
Fire Box Top Firebrick
3/20292
2-off