MI cable
Conduit bending tool
Figure 9: Use conduit bending tool for smaller bends
The relationship between cable diameter and minimum
bending radius is shown in Figure 10. When small bends
are necessary, do not try to make the entire bend in one
operation. Bend in small increments. Shape into final
position gradually. When offsetting the cable to enter
a junction box / equipment via a gland connector, at
least 2 to 3 in (50 to 75 mm) of straight cable should
be left between the gland connector and the final bend
to facilitate withdrawal of the gland connector from the
junction box / equipment.
(see Table 1)
Note: Bending radius shown for 0.75"
and smaller cables
Cable O.D.
Figure 10: Minimum bending radius
5 INSTALLATION
nVent.com | 17