Symptom
Probable Causes
Corrective Action
Insulation resistance is less than expected
1. Rain or high humidity.
2. Nicks or cuts in the cable
sheath, with moisture
present.
3. Kinked or crushed cable.
4. Arcing created by damage
to the cable.
5. Welding splatter.
6. Presence of moisture in
termination or temporary
seal.
7. Damaged termination or
temporary seal.
(1) Dry tails and face of seal.
Inspect power connection
box for moisture or signs or
tracking. Dry out connections
and retest.
(2, 3, 4, 5) Visually inspect
or fault locate cable to find
damaged section of cable.
Repair or replace cable or
contact nVent technical
support for assistance.
(6) Remove termination or
temporary seal. Dry out cable
following the procedure
in Appendix A. Replace
termination or seal.
(7) Replace termination or seal.
Short circuits and direct earth faults
1. Physical damage to cable
is causing a direct short
from conductor to sheath.
2. Misalignment of the
conductors within the seal
or incorrect and untidy
completion of the sheath
stripping procedure during
termination.
3. Conductors shorted to
sheath when cut at factory
(only for unterminated
cables)
(1) Check for visual
indications of damage
around any area where there
may have been maintenance
work. Repair or replace
damaged cable and/or
terminations.
(2) Remake termination.
(3) Remove short and
reseal end.
7 TROUBLESHOOTING GUIDE